簡要描述:監控(kong)設(she)備(bei)能(neng)接收多臺探(tan)測(ce)器(qi)的漏電、溫(wen)度信(xin)息,報(bao)(bao)警(jing)(jing)時(shi)發(fa)出(chu)聲(sheng)光報(bao)(bao)警(jing)(jing)信(xin)號,同時(shi)設(she)備(bei)上(shang)紅色“報(bao)(bao)警(jing)(jing)“指示燈亮(liang),顯(xian)示屏指示報(bao)(bao)警(jing)(jing)部(bu)位及(ji)報(bao)(bao)警(jing)(jing)類(lei)型,記錄報(bao)(bao)警(jing)(jing)時(shi)間(jian),聲(sheng)光報(bao)(bao)警(jing)(jing)一直保(bao)持,直至(zhi)按顯(xian)示屏“復(fu)位“按鈕遠(yuan)程對探(tan)測(ce)器(qi)實現復(fu)位。對于聲(sheng)音報(bao)(bao)警(jing)(jing)信(xin)號也可(ke)以使(shi)用顯(xian)示屏“消聲(sheng)“按鈕手動消除。琴臺式電氣(qi)火(huo)災(zai)監控(kong)主機(ji) 智慧消防(fang)系統(tong)集成
產品目錄Product center
相關文章Related articles
1 系統組成
1)站控(kong)管理層
站控(kong)管理(li)層針對(dui)電氣火災(zai)監(jian)控(kong)系(xi)統(tong)的管理(li)人員,是(shi)(shi)人機交互的直接窗口,也是(shi)(shi)系(xi)統(tong)的上(shang)層部分(fen)。主要由系(xi)統(tong)軟(ruan)件(jian)和必要的硬件(jian)設備,如觸摸屏(ping)、UPS電源等組成。監(jian)測系(xi)統(tong)軟(ruan)件(jian)對(dui)現場(chang)各類數據信息計算、分(fen)析、處理(li),并(bing)以圖(tu)形、數顯、聲(sheng)音、指示(shi)燈等方式反(fan)應現場(chang)運情況。
監(jian)控主機:用于(yu)數(shu)(shu)據(ju)采集、處理(li)(li)和數(shu)(shu)據(ju)轉發。為(wei)系(xi)(xi)統內或外(wai)部提供數(shu)(shu)據(ju)接口,進(jin)行系(xi)(xi)統管理(li)(li)、維護和分析(xi)工作。
UPS:保證(zheng)計算機監測系統(tong)(tong)的正常供電,在整(zheng)個系統(tong)(tong)發生供電問(wen)題(ti)時,保證(zheng)站控管理層設備的正常運行。
后臺監控設備設置在消控室中(zhong)。
2)網絡通訊(xun)層
通訊(xun)介質(zhi):系(xi)統主要采用(yong)屏蔽(bi)雙絞線,以MODBUS-RTU通訊(xun)協議(yi)實現(xian)現(xian)場(chang)設備與上位機的實時通訊(xun)。
3)現場設備層
現場設(she)備層是數據采(cai)集終端,主(zhu)要(yao)為ARCM200L-Z2剩余式電(dian)氣(qi)火(huo)災(zai)監(jian)控探測器。
系統結構(gou)拓撲圖如下:
2、電(dian)氣火災設(she)備
2.1、 Acrel-6000電氣(qi)火災監控后臺(tai):
主要技術參數
電源:
① 額定工作電壓AC220V(-15% ~ +10%)
② 備用電源:主電源欠壓或停(ting)電時(shi),維持監控設(she)備工作時(shi)間(jian) ≥4小時(shi)
工作制:
24小時(shi)工作制
通(tong)訊方式:
MODBUS-RTU通信(xin)協(xie)議
監控容量(liang):
① 監控設備可(ke)監控200個監控單元(探測器)
② 可配接ARCM系(xi)列(lie)監控(kong)探測(ce)器
監(jian)控報警項目:
① 剩(sheng)余(yu)電流故障(zhang)(漏電):故障(zhang)單元(yuan)屬性(部(bu)位、類(lei)型)
② 溫度報(bao)警(超溫): 故障單元屬(shu)性(部位、類型)
③ 電流故障(過(guo)流): 故障單元屬性(xing)(部位、類型)
監控報警(jing)響應時間: ≤30s
監控報警聲壓級(A計(ji)權):≥70dB/1m
監控(kong)報警光顯示:紅色LED指示燈,紅色光報警信號應保持,直(zhi)至手動復位
監控(kong)報(bao)警聲信號(hao):可(ke)手(shou)動(dong)消除,當(dang)再(zai)次有報(bao)警信號(hao)輸(shu)入時,能再(zai)次啟動(dong)
故(gu)障報警(jing)項目(mu):
① 監控設備與探測器之間(jian)的通(tong)訊(xun)連接(jie)線發生斷(duan)路(lu)或(huo)短路(lu)
② 監控設備(bei)主電(dian)源(yuan)欠壓或斷電(dian)
③ 給(gei)電池(chi)充電的充電器與電池(chi)之(zhi)間(jian)的連接線發生(sheng)斷(duan)路(lu)或短(duan)路(lu)
故障報警響應時間:≤100s
監控(kong)報警聲壓級(ji)(A計權):≥70dB/1m
監(jian)控報(bao)警光(guang)顯示:黃色LED指示燈,黃色光(guang)報(bao)警信號應保持至故障排除
故障報警聲信號:可手動消(xiao)除,當再次有報警信號輸(shu)入時(shi),能再次啟動
故障期間,非故障回路的正常工作(zuo)不受影響
控(kong)制(zhi)輸出:
報警控(kong)制(zhi)輸出:1組(zu)常開無源(yuan)觸(chu)點,容(rong)量:AC250V 3A或DC30V 3A
自檢(jian)項(xiang)目:
① 指示(shi)燈(deng)檢(jian)查:報(bao)警、故障、運行、主電源(yuan)、備用(yong)電源(yuan)指示(shi)燈(deng)
② 顯示屏檢查
③ 音響器件檢查
自檢耗時 ≤60s
事件(jian)記錄:
① 記錄內容:記錄類(lei)型、發生時間、探測(ce)器編號、區域、故障描(miao)述,可存儲記錄不(bu)少于2萬(wan)條
② 記錄(lu)(lu)查詢:根據記錄(lu)(lu)的(de)日期、類型等條件查詢
操作分級:
① 日常值班級:實時狀態監視(shi)、事(shi)件記(ji)錄查詢(xun)
② 監控(kong)操作級(ji):實時狀態監視、事(shi)件記錄查詢、探測器遠程復(fu)位、設備自檢
③ 系統管理級:實時(shi)狀態(tai)監(jian)視、事件記錄查詢、探測器遠程復(fu)位、設(she)備自(zi)檢,監(jian)控設(she)備系統參數查詢、監(jian)控設(she)備各模塊單獨檢測、操(cao)作員添加(jia)與(yu)刪(shan)除
使(shi)用環(huan)境條件:
① 工作場所:消防控制室內、有(you)人(ren)(ren)值班(ban)的變配(pei)電所(配(pei)電室)、有(you)人(ren)(ren)值班(ban)的房間(jian)內墻壁上
② 工作環境溫(wen)度:0℃~40℃
③ 工作環境相(xiang)對濕(shi)度:5%~95%RH
④ 海拔高度:≤2500m
3.2、ARCM200L系列(lie)儀表
ARCM200L 型剩(sheng)余電(dian)(dian)(dian)(dian)流(liu)式電(dian)(dian)(dian)(dian)氣火(huo)災(zai)監控(kong)探測器(qi)(qi),是(shi)針對(dui) 0.4kV 以下(xia)的(de)TT、TN 系(xi)統設計的(de),通(tong)過對(dui)配(pei)電(dian)(dian)(dian)(dian)回路(lu)的(de)剩(sheng)余電(dian)(dian)(dian)(dian)流(liu)、導(dao)線溫度(du)、過電(dian)(dian)(dian)(dian)流(liu)、過電(dian)(dian)(dian)(dian)壓等火(huo)災(zai)危險參數(shu)(shu)實施監控(kong)和管(guan)理(li),從(cong)而預防(fang)電(dian)(dian)(dian)(dian)氣火(huo)災(zai)的(de)發生,并實現(xian)了(le)對(dui)多種(zhong)電(dian)(dian)(dian)(dian)力(li)參數(shu)(shu)的(de)實時監測,為能(neng)耗(hao)管(guan)理(li)提供精確(que)的(de)數(shu)(shu)據。產品采用先進的(de)微控(kong)制器(qi)(qi)技術(shu),集(ji)成度(du)高(gao),體積小巧,安裝方便(bian),集(ji)智能(neng)化,數(shu)(shu)字(zi)化,網絡化于一(yi)身,是(shi)建筑電(dian)(dian)(dian)(dian)氣火(huo)災(zai)預防(fang)監控(kong)、系(xi)統絕緣老化預估等的(de)理(li)想(xiang)選擇。
3 系統功能
3.1.監控報警功能:
監控(kong)設備(bei)能接收多臺探測(ce)器的漏(lou)電、溫(wen)度信(xin)息,報警時(shi)(shi)發出聲(sheng)(sheng)(sheng)光報警信(xin)號(hao),同時(shi)(shi)設備(bei)上紅色“報警"指(zhi)示(shi)燈(deng)亮,顯示(shi)屏指(zhi)示(shi)報警部位(wei)及報警類型,記錄報警時(shi)(shi)間,聲(sheng)(sheng)(sheng)光報警一直保(bao)持(chi),直至(zhi)按顯示(shi)屏“復(fu)位(wei)"按鈕遠程對(dui)探測(ce)器實(shi)現(xian)復(fu)位(wei)。對(dui)于聲(sheng)(sheng)(sheng)音報警信(xin)號(hao)也(ye)可(ke)以使(shi)用顯示(shi)屏“消聲(sheng)(sheng)(sheng)"按鈕手動消除(chu)。
3.2.故障報警功(gong)能(neng)
通訊(xun)故(gu)(gu)障報警(jing):當監控(kong)(kong)設備(bei)與所接的任一臺探測(ce)器(qi)之間發生通訊(xun)故(gu)(gu)障時,監控(kong)(kong)畫(hua)面(mian)中相應(ying)的探測(ce)器(qi)顯示(shi)故(gu)(gu)障提示(shi),同時設備(bei)上的黃色(se)“故(gu)(gu)障"指(zhi)示(shi)燈亮,并發出故(gu)(gu)障報警(jing)聲音(yin)。
電(dian)源(yuan)故障報警(jing)(jing):當主電(dian)源(yuan)或備用電(dian)源(yuan)發生故障時,監(jian)控設(she)備也發出聲光報警(jing)(jing)信號(hao)并(bing)(bing)顯(xian)示(shi)故障信息,可進入(ru)相應的界(jie)面查看詳細信息并(bing)(bing)可解除報警(jing)(jing)聲響。
3.3.自(zi)檢功(gong)能
檢查設備(bei)中(zhong)所有狀態(tai)指示燈、顯示屏、喇叭是否(fou)正常。
3.4.報警記錄存儲查詢功能
當發生漏(lou)電、超溫報(bao)警或(huo)通訊、電源故障時(shi),將報(bao)警部位、故障信息、報(bao)警時(shi)間(jian)等信息存儲在數(shu)據庫中,當報(bao)警解(jie)除、排除故障時(shi),同(tong)樣(yang)予(yu)以(yi)記錄。歷史數(shu)據提供多種便捷、快速的查詢方(fang)法(fa)。
3.5.電源功能(neng)
當主(zhu)電源(yuan)發生停(ting)電、欠壓(ya)等(deng)故(gu)障時(shi),監控(kong)(kong)設備可自動切換到備用(yong)電源(yuan)工(gong)作,當主(zhu)電源(yuan)恢復正常供電時(shi),自動切回到主(zhu)電源(yuan),切換過(guo)程中(zhong)保證監控(kong)(kong)設備連續平穩運行。
34.6.對探測器控制功能
通過(guo)監控軟件操作,可對連接到本設備的所有探測(ce)器進行遠(yuan)程(cheng)復位控制。
3.7.權限控制功能
為確保監控(kong)系(xi)統的安(an)全運行,監控(kong)設備(bei)軟件(jian)操作(zuo)權限分為三(san)級(ji)(ji),不(bu)同(tong)(tong)級(ji)(ji)別的操作(zuo)員具(ju)有不(bu)同(tong)(tong)的操作(zuo)權限。
掃(sao)一掃(sao) 微信咨詢
©2024 安科瑞電氣股份有限公司 版權所有 技術支持: Sitemap.xml 總訪問量(liang):141148